CMCP-525 Vibration Acceleration Transmitter


CMCP-525 Vibration Acceleration Transmitter

Features:

  • Low Cost

  • Small Size

  • DIN Rail Mount

  • 4-20 mA Output

  • Fault Detection

  • Buffered Transducer Output

  • Filter Option

Approved


Description:
The CMCP-525 Vibration Acceleration Transmitters are compatible with piezo, voltage output accelerometer inputs, they provide a 4-20 mA output proportional to the overall measurement. Each unit provides power for the associated transducer, processes the vibration signal to determine overall amplitude, and outputs a 4-20 mA dc current that is proportional to a user specified range such as 0-5 g's RMS. Combining transmitters with an existing PLC or DCS system results in a high density, low cost vibration monitoring system. When specified with the alarm feature (CMCP-525A), the unit functions as a complete single channel monitor that includes alert and danger alarms, and output relays.

 

Buffered Output:
A BNC connector mounted on the front of the unit provides access to the buffered transducer output signal. This includes both the unfiltered vibration signal, and the DC bias voltage. Portable test equipment or analyzers like SKF-CM's MicrologTM can be connected to this output without disturbing other system outputs.

 

Fault Detection:
On board fault detection circuitry continuously monitors the transducer for normal operation. If a fault occurs, the output current is reduced to 2 mA to indicate the fault to the readout system. A red LED on the front of the unit is turned on to provide a local indication of the fault.

 

Filters:
For applications that require monitoring specific frequency bands, optional high-pass and low-pass filters can be specified. These filters are modular and can be installed by the factory or in the field. Each module attenuates out-of-band signals at a rate of approximately 24 dB/octave. Corner frequencies from 2 Hz to 20 kHz may be specified. Filter modules may be cascaded to form higher order filters or to create a band-pass response. Filtering does not effect the buffered transducer output.

 

Displays And Assemblies:
Various display options, NEMA and explosion-proof enclosures, and assembled multi-channel systems are available. Consult your sales representative.

Monitoring Systems

 

Electrical Specifications:

  • Power: +24 Vdc @ 45 mA max. (30 mA typical at 2 full scale output). Reverse polarity and transient protection   included.

  • Frequency Response (Without optional filters): (-3 dB) 2 Hz to 20 kHz.

  • Buffered Output: BNC Connector 0-20 kHz.

  • Accuracy: 5.0 % of Full Scale Range.

  • Output: 4-20 mA proportional to the full scale range.

  • Maximum Load: 600 Ohms Resistive.

  • Case: Isolated.

 

Environmental Specifications:

  • Operating Temp.: -20oC to +80oC (-4oF to +176oF).

  • Storage Temp.: -55oC to +125oC (-67oF to +257oF).

  • Relative Humidity: 0 - 95% Non-Condensing.

Mounting:
32 mm (G style) or 35 mm (T style) DIN Rail.

 

Ordering Example:

To order a standard acceleration transmitter that accepts input from a 100 mV/g Accelerometer, such as the SKF-CM CMSS786, with a Full Scale of 10 g with Peak Detection, specify Part Number: CMCP-525-100A-02P.

NOTES:

1.To order factory installed 4-pole filter modules, add the appropriate suffix to the basic part number:

Example: adding suffix -L500 specifies a 4-pole low-pass filter with a corner frequency of 500 Hz (30,000 cpm). Adding suffix - H40 specifies a 4-pole High-Pass filter with a corner frequency of 40 Hz (2400 cpm). Up to two filter modules may be specified. Filter modules can be field installed. If you are unsure about your filter needs, need higher order filters or a band-pass response, consult the factory or your regional sales office for assistance in specifying the correct option numbers.

2.The Full Scale option specified at order entry is used by the factory for initial calibration. However, several other ranges can be jumper selected in the field.

3.Transducer and Full Scale options not listed in the above table are available. Contact your sales representative.


Ordering Information:

 

Acceleration Monitor/Transmitter CMCP-525
CMCP-525(X)-(aaa)-(bbb)-(ccc)-(dddd)

CMCP-525, Acceleration Transmitter
CMCP-525A, Acceleration Monitor

(aaa) Input
100, 100 mV/g Accelerometer
Specify, Specify Exact mV/g

(bbb) Full Scale
01R, 0 to 5 g, RMS Detection
01P, 0 to 5 g, Peak Detection
02R, 0 to 10 g, RMS Detection
02P, 0 to 10 g, Peak Detection
Specify, Specify in 5 g Increments, Followed by
AR@ or AP@

(ccc) High Pass filter
HXX, High Pass Corner Frequency in Hz

(dddd) Low Pass Filter
LXXX, Low Pass Corner Frequency in Hz