CMCP-525A Vibration Acceleration Monitor |
|
 |
Features:
Approved
|
Description:
The CMCP-525A Vibration Acceleration Monitors are
compatible with piezo, voltage output accelerometer inputs, they provide a
4-20 mA output proportional to the overall measurement. Each unit provides
power for the associated transducer, processes the vibration signal to
determine overall amplitude, and outputs a 4-20 mA dc current that is
proportional to a user specified range such as 0-5 g's RMS. Combining
monitors with an
existing PLC or DCS system results in a high density, low cost vibration
monitoring system. With the specified alarm feature, the unit functions
as a complete single channel monitor that includes alert and danger alarms,
and output relays.
Buffered Output:
A BNC connector mounted on the front
of the unit provides access to the buffered transducer output signal. This
includes both the unfiltered vibration signal, and the DC bias voltage.
Portable test equipment or analyzers like SKF-CM's
MicrologTM can be connected to this output without disturbing
other system outputs.
Fault Detection:
On board fault detection circuitry
continuously monitors the transducer for normal operation. If a fault
occurs, the output current is reduced to 2 mA to indicate the fault to the
readout system. A red LED on the front of the unit is turned on to provide a
local indication of the fault.
Filters:
For applications that require
monitoring specific frequency bands, optional high-pass and low-pass
filters can be specified. These filters are modular and can be installed by
the factory or in the field. Each module attenuates out-of-band signals at a
rate of approximately 24 dB/octave. Corner frequencies from 2 Hz to 20 kHz
may be specified. Filter modules may be cascaded to form higher order
filters or to create a band-pass response. Filtering does not effect the
buffered transducer output.
Alarms:
This monitoring option adds
two independent set points, with LED alarm indicators and output relay
contacts (Alert and Danger). Set points are adjustable via potentiometer,
from 0 to 110% of full scale. Each has an adjustable delay of 1 to 10
seconds. Relay contacts can be independently configured by the user for
either Normally Open (NO) (Standard) or Normally Closed (NC) operation.
Relays are normally de-energized and can be configured for latching or
non-latching (standard) operation. Latched alarms may be reset locally or by
remote contact closure. SPST Relay contacts are rated 5 Amps @ 30 Vdc or 250
Vac for resistive loads. The Alarm option also provides set point
multiplication of 3X via contact closure (2X available).
Displays And Assemblies:
Various display options, NEMA
and explosion-proof enclosures, and assembled multi-channel systems are
available. Consult your sales representative.
Monitoring Systems
Electrical Specifications:
-
Power: +24 Vdc @ 45 mA max.
(30 mA typical at 2
full scale output). Reverse polarity and transient protection
included. (With the Alarm/Relay option installed: 75 mA max.)
-
Frequency Response (Without optional filters): (-3 dB) 2 Hz to 20
kHz.
-
Buffered Output: BNC Connector 0-20 kHz.
-
Accuracy: 5.0 % of Full Scale Range.
-
Output: 4-20 mA proportional to the full scale range.
-
Maximum Load: 600 Ohms Resistive.
-
Case: Isolated.
Environmental Specifications:
-
Operating Temp.: -20oC to +80oC
(-4oF to +176oF).
-
Storage Temp.: -55oC to +125oC (-67oF
to +257oF).
-
Relative Humidity: 0 - 95% Non-Condensing.
Mounting:
32 mm (G style) or 35 mm (T style) DIN Rail.
Ordering Example:
To order a standard
acceleration monitor that accepts input from a 100 mV/g Accelerometer, such
as the SKF-CM CMSS786, with a Full Scale of 10 g with Peak Detection,
specify Part Number: CMCP-525A-100A-02P.
NOTES:
1.To order factory installed
4-pole filter modules, add the appropriate suffix to the basic part
number:
Example: adding suffix
-L500 specifies a 4-pole low-pass filter with a corner frequency of 500
Hz (30,000 cpm). Adding suffix - H40 specifies a 4-pole High-Pass filter
with a corner frequency of 40 Hz (2400 cpm). Up to two filter modules
may be specified. Filter modules can be field installed. If you are
unsure about your filter needs, need higher order filters or a band-pass
response, consult the factory or your regional sales office for
assistance in specifying the correct option numbers.
2.The Full Scale option
specified at order entry is used by the factory for initial calibration.
However, several other ranges can be jumper selected in the field.
3.Transducer and Full Scale
options not listed in the above table are available. Contact your sales
representative.
Ordering
Information:
Acceleration Monitor/Transmitter CMCP-525
CMCP-525(X)-(aaa)-(bbb)-(ccc)-(dddd)
CMCP-525, Acceleration Transmitter
CMCP-525A, Acceleration Monitor
(aaa) Input
100, 100 mV/g Accelerometer
Specify, Specify Exact mV/g
(bbb) Full Scale
01R, 0 to 5 g, RMS Detection
01P, 0 to 5 g, Peak Detection
02R, 0 to 10 g, RMS Detection
02P, 0 to 10 g, Peak Detection
Specify, Specify in 5 g Increments, Followed by
AR@
or AP@
(ccc) High Pass filter
HXX, High Pass Corner Frequency in Hz
(dddd) Low Pass Filter
LXXX, Low Pass Corner Frequency in Hz
|
|