CMCP-5301 and CMCP-5302

 1 and 2 Channel General Machinery Monitors


Features:

  • Two Levels of Alarm with Relays

  • True “OK” Circuitry with Relay

  • Adjustable Time Delays

  • Trip Multiply

  • 4-20mA Output

  • Buffered Transducer Output

  • Reset Button

  • Bright LED Digital Readout

The CMCP-5301 and CMCP-5302 are one and two channel Vibration Monitors that have been designed for use on typical rotating machinery such as motors, pumps fans, turbines, compressors, chillers., etc.

 

The CMCP-5301 and 5302 accept inputs from any industry standard 100 mV/g accelerometer, condition’s the input signals to velocity and provides a digital display and alarm status indication. Analog outputs (4-20 mA) are provided for each channel for interface to a PLC or DCS for trending, alarm and operator interface. The alarm contacts for the OK circuit, and Alert and Danger may be interfaced to machine control and shutdown systems for a complete vibration protection solution.

 

The system is a pre-wired turn-key package with power supply, and bright LED display(s). The power supply accepts 110 or 220 VAC, 50 or 60 Hz. They are available in either an English or Metric configuration.

 

The CMCP-5301 and CMCP-5302 are also available with any other CMCP-500 Series Monitor.

 

Specifications:

Electrical

Power:

Accepts 110 VAC or 220 VAC, 60 or 50 Hz

Frequency Response:

(-3 dB) 2 Hz to 20 kHz

Buffered Output:

BNC Connector 0-20 kHz

Accuracy:

5.0 % of Full Scale Range

Output:

4-20 mA proportional to the full scale range

Relay output for Alert and Danger alarms

Maximum Load:

600 Ohms Resistive per channel

Case:

Isolated

Environmental

Operating Temp.:

-20oC to +80oC (-4oF to +176oF)

Storage Temp.:

-55oC to +125oC (-67oF to +257oF)

Relative Humidity:

0 - 95% Non-Condensing

Approvals: NEMA 4X Fiberglass
Physical
Dimensions: Width: 7.25”, Height: 7.25”, Depth: 5.00”

 

Ordering Information:

CMCP-5301

-XX

-X

One Channel Monitoring System

CMCP-5302

-XX

-X

Two Channel Monitoring System

 

-01

 

No Display

 

-02

 

With Individual Displays

 

 

-E

English 0-1.0 in/sec

 

 

-M

Metric 0-25.0 mm/sec

 

Download Data Sheet in PDF Format