CMCP510
Displays may be recalibrated in the field for a full scale reading of
000 to 1999. Displays are calibrated at the factory per order to match
the requirements specified by the customer. If the full scale range of
the CMCP500 Series Transmitter is changed in the field the display must
be recalibrated to the new full scale range.
Using a
4-20mA loop calibrator, such as an Altek 334A, connect the leads of the
calibrator as shown in the drawing below.
Setting
the 4 mA Set Point (Zero Scale):
Apply 4
mA to the CMCP510 input. Using a small flathead screwdriver, adjust R3
until the desired reading is achieved. See Charts Below
Setting
the 20 mA Set Point (Full Scale):
Apply
20 mA to the CMCP510 input, adjust R7 until the desired reading is
achieved. See Charts Below
Check
to be sure Zero Scale is correct.
|
Display Reading |
|
4mA |
20 mA |
DIP Switch 1 |
Dip Switch 2 |
Dip Switch 3 |
|
000 |
1050 to 1999 |
Off |
Off |
Off |
|
000 |
650 to 1350 |
On |
Off |
Off |
|
000 |
450 to 800 |
Off |
On |
Off |
|
000 |
300 to 500 |
Off |
Off |
On |
|
000 |
200 to 300 |
On |
On |
On |

|
Decimal Point Placement Guideline: |
|
In/Sec (0.000) |
Dip Switch 4 |
DIP Switch 5 |
Dip Switch 6 |
|
mm/sec (00.00) |
Off |
Off |
On |
|
mils (00.00) |
Off |
On |
Off |
|
microns (0000) |
Off |
Off |
Off |
|
Temperature (000.0) |
On |
Off |
Off |